Summary
Description
Technical Challenge
Results
Conclusions
Download
Back to Case
Studies
|
|
|
|
LV Losses - Summary Very
high load losses in the LV winding have been observed. The LV
winding was built following the “classical” design rules for the
transposition of conductors in parallel. However, only simulations
can verify the validity of the “classical solution” for each
specific design.
Simulations show that the flux leakage pattern is not symmetrical
and with significant radial components.
The radial transpositions in the LV winding, determined by means of
classical rules are not sufficient to keep circulating currents
under control. The axial positioning of transpositions minimizing
the losses without additional costs for the winding is determined.
Description
|
|
|