GSU Transformer Upgrade – Tank Hot Spot - Results
 |
|
Specific losses (original
enclosure) |
 |
|
Temp. at 190 MVA,
tank
flange hot spot = 96°C |
|
 |
|
Specific losses (new enclosure) |
|
 |
|
Temp. at 228 MVA,
tank flange hot spot =
72°C |
The solution was to move the crossover shorting plate to shift
flux induced currents and losses from the tank cover flange to the
middle of the tank cover.
Conclusions |
|
|