Converter Transformer Load Losses - Summary
Locally the LV-winding had very high losses, causing
conductors to overheat with consequent turn to turn failure.
Because of the small amount of cellulose being degraded, the
Dissolved Gas Analyses (DGA) may not alert the end user
about the imminent failure.
The simulation provided an
excellent match with the observed failure (burnt paper at middle
axial height of LV-winding). It allowed the OEM to understand the
nature of the failure and take proper corrective actions.
If the simulation had been used to validate the original design, the
failure would have not occurred!
Description